8
Service
Fault table standard
Operating Instructions – MOVIMOT
®
flexible
261
Subfault: 45.5
Description: Engineering interface
Response: Warning
Cause
Measure
Engineering interface no longer works, or works
only to a limited extent.
– Switch the power off and on again/perform a re-
set.
– If the fault occurs repeatedly, replace the field-
bus card and send it to SEW-EURODRIVE to-
gether with the fault number. For further support,
contact SEW-EURODRIVE Service.
Subfault: 45.7
Description: Invalid process output data
Response: Fieldbus – timeout response
Cause
Measure
– The producer of the process output data reports
that the data is invalid.
– Process data is exchanged via the fieldbus but
the data is invalid.
– Check whether the PLC is in "Stop" state.
– Restart the PLC.
Subfault: 45.9
Description: Fieldbus interface – warning
Response: Warning
Cause
Measure
Basic unit detects non-critical fault on internal in-
terface for fieldbus connection.
– Reset the fault.
– If the fault occurs repeatedly, replace the field-
bus card and send it to SEW-EURODRIVE to-
gether with the fault number. For further support,
contact SEW-EURODRIVE Service.
Subfault: 45.50
Description: Fieldbus card – warning
Response: Warning with self reset
Cause
Measure
Fieldbus interface signals subcomponent fault of
the type "warning".
Refer to the subcomponent fault of the fieldbus
interface and perform the action required for elim-
inating the fault.
Subfault: 45.51
Description: Fieldbus card – fault
Response: Fieldbus – timeout response
Cause
Measure
Fieldbus interface signals subcomponent fault of
the type "standard".
Refer to the subcomponent fault of the fieldbus
interface and perform the action required for elim-
inating the fault.
29128668/EN – 12/2019