USER MANUAL – Z-TWS4/Z-PASS2-S/S6001-RTU
198
The FB has the following input parameters:
- SERVER_ADDR : OPC UA Server URL (e.g.:
opc.tcp://192.168.90.2:53530/OPCUA/SimulationServer)
- USER_NAME : user name for authentication
- USER_PSW : password for authentication
- @ENABLE : TRUE -> FB is executed
FALSE -> FB is skipped
The FB has the following output parameters:
- RESULT : -2, when called with ENABLE=FALSE
-1, in case of any failure
0, if the process is still running
1, if the process has successfully finished
- CONN_ID : connection identifier, to be used in UAC_READ, UAC_WRITE and
UAC_DISCONNECT FB
19.1.24
UAC_DISCONNECT
This Function Block can be used to disconnect from an OPC-UA Server.
When first called, it runs a process which starts the procedure;
on subsequent calls, it only checks if the process has finished its job.
The FB has the following input parameters:
- CONN_ID : connection identifier, given by the UAC_CONNECT FB
- @ENABLE : TRUE -> FB is executed
FALSE -> FB is skipped
The FB has the following output parameters:
- RESULT : -2, when called with ENABLE=FALSE
-1, in case of any failure
0, if the process is still running
1, if the process has successfully finished
19.1.25
UAC_READ
Summary of Contents for S6001-RTU
Page 35: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 35 Then import the Library menu Tools Import...
Page 68: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 68...
Page 76: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 76...
Page 86: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 86...
Page 87: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 87...
Page 121: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 121...
Page 133: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 133...
Page 162: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 162 Select the mbus_shm csv file...