SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
144/
150
5.17.
Expansion Board Configuration Menu
5.17.1.
Overview
NOTE
Parameters in this menu are
Rxxx
parameters.
Once saved, they have no effect until the drive is next powered on, or until
the control board is reset by holding down the
RESET
key for more than 5
secs.
5.17.2.
List of Programmable Parameters R021 to R023
Paramete
r
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
R021
Data Logger Setting
ENGINEERING
551
1: Disable
R023
I/O Board Setting
ENGINEERING
553
0: None
Table 35: List of parameters R021 to R023
R021 Data Logger Setting
R021
Range
1
2
1: Disable
2: Enable
Default
1
1: Disable
Level
ENGINEERING
Address
551
Function
This parameter enables or disables Data Logger initialization (if the
ES851 Data Logger board is fitted).
R023 I/O Board Setting
R023
Range
0
6
0: None
1: XMDO
2: XMDO + Pout
3: XMDO + PT100
4: XMDO + Pout + PT100
5: XMDO + ADE + PT100
6: XMDO + ADE + PT100 + Pout
Default
0
0: None
Level
ENGINEERING
Address
553
Function
Based on the settings in the respective parameters, this parameter
enables controlling the following items:
XMDO: Digital OUTPUTS (see the Auxiliary Digital Outputs Menu);
Pout: DC measures (see the DC Measures Settings Menu);
PT100: Up to 4 PT100 probes (see the PT100);
ADE: Energy measures through ADE7758 (see the ADE Registers
Settings Menu).
NOTE
ES847 is required to control DC measures, PT100 probes and energy
measures via ADE7758.
Both ES847 and ES870 can be used for controlling XMDO digital outputs.