P571 Min. Voltage Alarm Enable
P571
Range
0
0007h
0
0007
Default
0007h
Bit 0
1 Enable R phase alarm
Bit 1
1 Enable S phase alarm
Bit 2
1 Enable T phase alarm
Level
ENGINEERING
Address
691
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS min. voltage alarm of the three mains phases (R, S, T).
P572 Max. Voltage Alarm Enable
P572
Range
0
0007h
0
0007
Default
0007h
Bit 0
1 Enable R phase alarm
Bit 1
1 Enable S phase alarm
Bit 2
1 Enable T phase alarm
Level
ENGINEERING
Address
692
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS max. voltage alarm of the three mains phases (R, S, T).
P573 RMS Alarm enable
P573
Range
0
0007h
0
0007
Default
0007h
Bit 0
1 Enable R phase alarm
Bit 1
1 Enable S phase alarm
Bit 2
1 Enable T phase alarm
Level
ENGINEERING
Address
693
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS voltage alarms of the three mains phases (R, S, T).
P574 Frequency Alarm Enable
P574
Range
0
0003h
0
0003
Default
0003h
Bit 0
1 Enable Max. Frequency alarm
Bit 1
1 Enable Min. Frequency alarm
Level
ENGINEERING
Address
694
Function
Bit-controlled parameter: bits 0 to 1 allow enabling (Bit = 1) or disabling
(Bit = 0) the mains Max. and Min. frequency alarms.
P575 Instantaneous Overvoltage Alarm Enable
P575
Range
0
0007h
0
0007
Default
0007h
Bit 0
1 Enable Phase R Alarm
Bit 1
1 Enable Phase S Alarm
Bit 2
1 Enable Phase T Alarm
Level
ENGINEERING
Address
695
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) each individual Instantaneous Overvoltage alarm of the three
phases of the mains.