SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
140/
150
C164a C165a C166a External Alarm Trip Delay
C164a
C165a
C166a
Range
0
32000
0
32000 msec
Default
0
Instantaneous
Level
BASIC
Address
1305, 1306, 1307
Function
Trip delay of the external alarm. This is a delay time allowing checking
if the input set as “external alarm” is open before the alarm trips.