SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
128/
150
5.11.3.
Exchanged Parameters
The tables below cont
ain the Sinus Penta’s parameters that are exchanged via Fieldbus.
Each table includes:
1) The parameter number (ID);
2) Its description;
3) Its setting range;
4) Its unit of measure (which is also displayed on the display/keypad);
5) The ratio between the value internal to the Regenerative Sinus Penta (which is exchanged via
Fieldbus) and the hardware represented value (as displayed).
NOTE
Each parameter is exchanged as a 16-bit integer with a ± sign (from
–
32768 to +32767). The byte exchanging sequence follows the
big-endian
rule (i.e. the most significant value is stored to the lowest address).
5.11.4.
From the Master to the Sinus Penta
Word
1) ID
2) Description
3) Range
4) Unit of
Measure
5) Ratio
1÷4
–
not used
–
–
–
5
M035
Digital inputs from
FIELDBUS
–
–
–
6
Commands for digital
outputs from FIELDBUS
–
–
–
7
AO1
Analog Output 1
controlled via FIELDBUS
+ 167
+ 2833
–
–
8
AO2
Analog Output 2
controlled via FIELDBUS
+ 167
+ 2833
–
–
9
AO3
Analog Output 3
controlled via FIELDBUS
+ 167
+ 2833
–
–