P321/P323/P325/P327 Measure Offset in Channels 1/2/3/4
P321 / P323 /
P325 / P327
Range
–30000 ÷ 30000
–300.00 ÷ 300.00°C
Default
0
0.00°C
Level
ENGINEERING
Address
921/923/925/927
Function
Value of the measure offset: an offset can be applied to the measure to
correct possible errors.
P320a/P322a/P324a/P326a Alarm Level for Channels 1/2/3/4
P320a / P322a /
P324a / P326a
Range
–50 ÷ 260
–50°C ÷ 260°C
Default
260
260°C
Level
ENGINEERING
Address
918/919/928/929
Function
Alarm threshold for
A105
..
A108
.
Alarms trip when measures > levels.