SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
100/
150
P510 DC-bus Voltage Regulator
Proportional Term with Min. Error
P510
Range
0
65000
0
65.000
Default
Level
ENGINEERING
Address
620
Function
This parameter sets the proportional term of the DC-bus voltage
regulator for an error lower than or equal to the min. error threshold.
P510
=1: with a regulation error of 1V of the DC-bus voltage, the drive
shall deliver 1 Ampere.
If the min. error threshold is the same as the max. error threshold
(
P514
=
P515
), the proportional term used by the regulator is always
P510
.
P511 DC-Bus Voltage Regulator
Integral Term with Min. Error
P511
Range
0
65000
0
649.99 ms with 650.00
Disable
Default
Level
ENGINEERING
Address
621
Function
This parameter sets the integral term of the DC-bus voltage regulator.
If the minimum and maximum error threshold match (
P514
=
P515
), the
integral term used in the regulator is always
P511
, independently of the
error value.
P512 DC-Bus Voltage Regulator
Proportional Term with Max. Error
P512
Range
0
65000
0
65.000
Default
Level
ENGINEERING
Address
622
Function
This parameter sets the proportional term of the DC-bus voltage
regulator when the error exceeds the maximum error threshold.
P512
=1: with a regulation error of 1V of the DC-bus voltage, the drive
shall deliver 1A current.
It activates and can be displayed only if
P515
>
P514
.
P513 DC-Bus Voltage Regulator
Integral Term with Max. Error
P513
Range
0
65000
0
649.99 ms with 650.00
Disable
Default
Level
ENGINEERING
Address
623
Function
This parameter sets the integral term of the DC-bus when the error
exceeds the maximum error threshold.
It activates and can be displayed only if
P515
>
P514
.