3.5.
Short-Circuit Currents
Short-circuit current is referred to the maximum power of the drive. All the drive models are sized based on
the fault current values (Standard Fault Current) according to UL508C and are protected internally by solid
state systems. The operation and manufacturing process of such systems comply with UL508C.
CLASSES 2T-4T
Size
Model of
SINUS PENTA
REGENERATIVE
Drive
Short-circuit
current
kA
S05 2T
all models
5
S12 2T
all models
5
S05 4T
all models
5
S12 4T
0016..0030
5
0034..0036
10
S15
all models
10
S20
all models
10
S30
all models
10
S41
0180..0202
18
0217..0260
30
S51
0313..0367
30
0402
42
S60
all models
42
S64/S65
all models
85
S74/S75
0964..1130
150
1296
200
S84/S90
all models
200
CLASSES 5T-6T
Size
Model of
SINUS PENTA
REGENERATIVE
Drive
Short-circuit
current
kA
S12 5T
all models
5
S14
0003..0022
5
0024..0032
10
S22
all models
10
S32
0076
10
0088..0164
18
S42
0181..0259
30
S52
0290..0401
42
S64/S65
all models
85
S64/S70
all models
150
S74/S75
all models
150
S74/S80
all models
200
S84/S90
all models
200