GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
85/
150
4.1.
Firmware Upgrade
This section covers firmware upgrade and application download.
NOTE
In case of multidrop connection (RS485), only the equipment to be upgraded
shall be connected to the network.
1
Launch the Remote Drive.
2
Select the dialog language (click a flag) and press Next.
3
In the “Connection Parameters” window, select the Local mode. In the “Serial Configuration
Parameters” window, set the interface device, the COM being used and the baud rate (38400bps); click
“Connect”, then click the “Next” button.
In the example below, USB-RS485 converter is used.
4
Select “Firmware Upgrade” from the “File” drop-down menu. Enter the path for the PXxxxxF0.mot and
PXxxxxF1 files to be downloaded.
If only one of the firmware files or MMI tables is to be updated, go to step 7. If an application shall be
downloaded to a PXxxxx, select the PXxxxxF0.mot file and click the “Open” button.