GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
111/
150
5.5.
DC Measures Settings Menu
5.5.1. Overview
This menu allows calibrating DC current measures (detected with an optional, external current transducer;
see Additional C
omponents for the “Energy Counter” Application) in Menu n.3 – DC Measures.
It can be viewed only if parameter
R023
=
2:XMDO+Pout, or
4:XMDO+PT100+Pout, or
6:XMDO+ADE+PT100+Pout (see the Expansion Board Configuration Menu).
5.5.2. List of Programmable Parameters P545 to P547
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P545
DC Current Offset
ENGINEERING
998
0.00 mA
P546
DC Current Input Filter
ENGINEERING
999
100 ms
P547
LEM Coil Ratio for XAIN7
ENGINEERING
991
2000
Table 18: List of parameters P545 to P547
P545 DC Current Offset
P545
Range
–2000
2000
– 20.00 mA
+20.00 mA
Default
0
0.00 mA
Level
ENGINEERING
Address
998
Function
This parameter selects the offset correction value of the DC current signal
that has been measured.
The set value is added to the signal measured before saturation or
conversion.
P546 DC Current Input Filter
P546
Range
0
65000
0
65000 ms
Default
100
100 ms
Level
ENGINEERING
Address
999
Function
This parameter selects the value of the time constant for the first order
low-pass filter applied to the DC current signal at the end of the signal
conversion and saturation chain.
P547 LEM Coil Ratio for XAIN7
P547
Range
1
65535
1
65535
Default
2000
2000
Level
ENGINEERING
Address
991
Function
This parameter sets the coil ratio between the primary and the
secondary of the LEM current transducer used for calculating the DC
Power value.