GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
107/
150
P531a/b/c Phase R/S/T Voltage RMS Gain
P531a/b/c
Range
–2048
+2047
1
50%
Default
0
1
Level
ENGINEERING
Address
958/959/960
Function
This gain affects both the voltage RMS value and the apparent power
RMS value.
V=V*(1+(P531/2
12
))
The overall calibration range is then 1
50%.
P532a/b/c Phase R/S/T Current RMS Gain
P532a/b/c
Range
–2048
+2047
1
50%
Default
0
1
Level
ENGINEERING
Address
961/962/963
Function
This gain affects both the current RMS value and the apparent power
RMS value.
I=I*(1+(P532/2
12
))
The overall calibration range is then 1
50%.
P533a/b/c Phase R/S/T Active Power Gain
P533a/b/c
Range
–2048
+2047
1
50%
Default
0
1
Level
ENGINEERING
Address
964/965/966
Function
This register calibrates the calculation of Active Power P.
P=P*(1+(P533/2
12
))
The overall calibration range is then 1
50%.
P534a/b/c Phase R/S/T Reactive Power Gain
P534a/b/c
Range
–2048
+2047
1
50%
Default
0
1
Level
ENGINEERING
Address
967/968/969
Function
This register calibrates the calculation of Reactive Power Q.
Q=Q*(1+(P534/2
12
))
The overall calibration range is then 1
50%.