5.16.
Autoreset Menu
5.16.1.
Overview
The Autoreset function can be enabled in case an alarm trips. You can enter the maximum number of
autoreset attempts and the time required for resetting the attempt number. If the Autoreset function is
disabled, you can program an autoreset procedure at power on, which resets an active alarm when the drive
is shut off. Undervoltage alarms or mains loss alarms can be saved in the fault list in the Autoreset menu.
To activate the Autoreset function, set a number of attempts other than zero in parameter
C255
. If the
number of attempts reset within a time interval t <
C256
is equal to the value set in
C255
, the autoreset
function is disabled; it will be enabled again only when a time longer than or equal to
C256
has passed.
If the drive is turned off when an alarm is active, the alarm tripped is stored to memory and will be active at
next power on. Regardless of the Autoreset function setup, an automatic reset of the last alarm stored can
be obtained when the drive is next turned on (
C257
[Yes]).
5.16.2.
List of Programmable Parameters C255 to C261
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
C255
Autoreset Attempt Number
ENGINEERING
1255
4
C256
Attempt Counting Reset Time
ENGINEERING
1256
300 sec
C257
Alarm reset at Power On
ENGINEERING
1257
0: [Disabled]
C258
Enable TLP Fault Autoreset
ENGINEERING
1258
0: [Disabled]
C259
Enable CFilt Fault Autoreset
ENGINEERING
1259
0: [Disabled]
C260
Enable Mains Fault Autoreset
ENGINEERING
1260
0: [Disabled]
C261
Enable External Alarm Autoreset
ENGINEERING
1261
0: [Disabled]
Table 34: List of parameters C255 to C261
C255 Autoreset Attempt Number
C255
Range
0 ÷ 10
0 ÷ 10
Default
4
4
Level
ENGINEERING
Address
1255
Functio
n
If set different from Disable (Disable = 0), this parameter enables the
Autoreset function and sets the max. number of reset attempts for a time
interval set in
C256
. If a time equal to the time set in
C256
passes starting
from the last alarm tripped, the autoreset attempt count is reset.
C256 Attempt Counting Reset Time
C256
Range
0 ÷ 1000
0 ÷ 1000 sec
Default
300
300 sec
Level
ENGINEERING
Address
1256
Functio
n
This parameter sets the time that passes from the last alarm tripped to reset
the autoreset attempt number.