SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
134/
150
5.12.2.
List of Programmable Parameters C500 to C503
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
C500
Rated Mains Voltage
BASIC
1000
Depending on
voltage class
C501
Rated Mains Frequency
BASIC
1001
50.0 Hz
C502
Mains Fault Enable
ENGINEERING
1002
1: Yes
C503
Motor Drive Enabling Mode
ADVANCED
1003
2:REGEN RUN
Table 28: List of parameters C500 to C503
C500 Rated Mains Voltage
C500
Range
Class 2T
1000
2400
Class 4T
1000
4800
Class 5T
1000
5750
Class 6T
1000
6900
Class 2T
100,0
240,0 V
Class 4T
100,0
480,0 V
Class 5T
100,0
575,0 V
Class 6T
100,0
690,0 V
Default
Class 2T
2300
Class 4T
4000
Class 5T
5750
Class 6T
6900
Class 2T
230.0 V
Class 4T
400.0 V
Class 5T
575.0 V
Class 6T
690.0 V
Level
BASIC
Address
1000
Function
This parameter sets the rated mains voltage used to calculate the trip
thresholds of the mains alarms that can be set through the parameters
included in the Mains Monitor menu (
P550
etc.).
C501 Rated Mains Frequency
C501
Range
400
700
40.0
70.0 Hz
Default
500
50.0 Hz
Level
BASIC
Address
1001
Function
This parameter sets the rated mains frequency used to calculate the
min./max. frequency thresholds set through parameters
P562
and
P566
in the Mains Monitor menu.