GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
123/
150
5.9.
Auxiliary Digital Outputs Menu
5.9.1. Overview
Auxiliary digital outputs XMDO1...6 can be programmed using the parameters contained in this menu.
This menu can be viewed only if parameter
R023
0 (see the Expansion Board Configuration Menu).
5.9.2. List of Programmable Parameters P582 to P593
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P582
XMDO1: Signal Selection
ENGINEERING
702
D0: Disable
P583
XMDO1: Output Logic Level
ENGINEERING
703
1: True
P584
XMDO2: Signal Selection
ENGINEERING
704
D0: Disable
P585
XMDO2: Output Logic Level
ENGINEERING
705
1: True
P586
XMDO3: Signal Selection
ENGINEERING
706
D0: Disable
P587
XMDO3: Output Logic Level
ENGINEERING
707
1: True
P588
XMDO4: Signal Selection
ENGINEERING
708
D0: Disable
P589
XMDO4: Output Logic Level
ENGINEERING
709
1: True
P590
XMDO5: Signal Selection
ENGINEERING
710
D0: Disable
P591
XMDO5: Output Logic Level
ENGINEERING
711
1: True
P592
XMDO6: Signal Selection
ENGINEERING
712
D0: Disable
P593
XMDO6: Output Logic Level
ENGINEERING
713
1: True
Table 23: List of parameters P582 to P593
P582/584/586/588/590/592 Variable Selected for Auxiliary Digital Outputs XMDO1/6
Range
0
11
0: Synchronism OK
1: Run OK
2: Mains Fault
3: Drive OK
4: Alarm Tripped
5: W40 Fan Fault
6: Pre-charge OK
7: Command 1 from Fieldbus
8: Command 2 from Fieldbus
9: Command 3 from Fieldbus
10: Command 4 from Fieldbus
11: Fan ON
Default
3
3: Drive OK
Level
ENGINEERING
Address
702/704/706/708/710/712
Function
These parameters set the functions implemented from digital outputs
XMDOx. See Table 22 for detailed functions.
P583/585/587/589/591/593 Logic Applied to Auxiliary Digital Outputs XMDO1/6
Range
0
1
0: FALSE
1: TRUE
Default
1
1: TRUE
Level
ENGINEERING
Address
703/705/707/709/711/713
Function
XMDOx
digital output logic function to apply a logic reversal (negation)
to the calculated output signal:
(0) FALSE = a logic negation is applied;
(1) TRUE = no negation is applied.