GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
117/
150
P561 Instantaneous Undervoltage Reset Time
P561
Range
1
1000
0.001
1.000 s
Default
10
0.010 s
Level
ENGINEERING
Address
681
Function
This is the time when the instantaneous undervoltage reset condition is
maintained to deactivate the mains Instantaneous Undervoltage fault.
P562 Max. Frequency Trip Threshold
P562
Range
10
200
0.10
2.00 Hz
Default
30
0.30 Hz
Level
ENGINEERING
Address
682
Function
This parameter sets the max. frequency value if compared to the rated
frequency which determines the mains Max. Frequency fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P563 Max. Frequency Release Ratio
P563
Range
995
1000
0.995
1.000
Default
998
0.998
Level
ENGINEERING
Address
683
Function
This parameter sets the ratio between the trip frequency for the Max.
Frequency fault and its reset value.
P564 Max. Frequency Trip Time
P564
Range
40
1000
0.040
1.000 s
Default
80
0.080 s
Level
ENGINEERING
Address
684
Function
This is the time when the max. frequency trip condition is maintained for
the mains Max. Frequency fault.
If
P576
>0, the value in this parameter is affected by the regulations
selected and can no longer be changed.
P565 Max. Frequency Reset Time
P565
Range
40
1000
0.040
1.000 s
Default
100
0.100 s
Level
ENGINEERING
Address
685
Function
This is the time when the max. frequency reset condition is maintained to
deactivate the mains Max. Frequency fault.