SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
110/
150
P540 NoLoad Threshold
P540
Range
0
1
0
Disable
1
Enable
Default
0
0
Disable
Level
ENGINEERING
Address
953
Function
If the active power drops below 0.005% of the full-scale value, energy
accumulation can be suspended when this happens.
Disable: disabled threshold
energy is always accumulated.
Enable: enabled threshold
energy is not accumulated if P<0.005%.
P542 CT Coil Ratio for ADE
P542
Range
1
65535
1
65535
Default
Level
ENGINEERING
Address
992
Function
This parameter indicates the coil ratio between the primary and the
secondary of the CTs used for calculating the AC power value.
I003 Energy Counter Reset
I003
Range
0
1
0
No
1
Yes
Default
This is not a parameter: I003 is set to zero at power on and whenever
the command is executed.
Level
ENGINEERING
Address
1390
Function
0
Inactive;
1
Both energy counters are reset (measures can be viewed in
M537
(Active Energy) and
M539
(Reactive Energy).