GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
101/
150
P514 DC-Bus Voltage Regulator
Min. Error Threshold
P514
Range
1
65000
0.001
65.000%
Default
2000
2.000%
Level
ENGINEERING
Address
624
Function
Min. error threshold.
If
P514
=
P515
or if the DC-bus voltage regulation error is lower than or
equal to
P514
, the DC-bus voltage regulator only uses proportional and
integral terms
P510
and
P511
.
For the regulator functioning with
P515
>
P514
, see the section above.
P515 DC-bus Voltage Regulator
Max. Error Threshold
P515
Range
1
65000
0.001
65.000%
Default
14000
14.000%
Level
ENGINEERING
Address
625
Function
Max. error threshold.
If
P515
>
P514
, the regulator parameters relating to max. error
P512
and
P513
activate and can be displayed. In that case, if the regulation error is
higher than or equal to
P515
, the DC-bus voltage regulator only uses
proportional and integral terms
P512
and
P513
.
For the regulator functioning with
P515
>
P514
, see the section above.
P516 Regenerative Inductance
P516
Range
50
32000
0.050
32.000mH
Default
Depends on size and voltage class; see sections Regenerative Reactors
for 2T Voltage Class and Regenerative Reactors for 4T Voltage Class,
and Regenerative Reactors for 5T-6T Voltage Class.
Level
ENGINEERING
Address
626
Function
Value of the regenerative reactor.
The default value of this parameter is the rated value of the reactor which
is normally applied to the input of the regenerative drive and which is
recommended by Elettronica Santerno.
NOTE
The setting of
P516
should be changed only if the regenerative reactor being
used has different ratings than the default value set by Elettronica Santerno.