5.10.
PT100 Measures Menu
5.10.1.
Overview
This menu allows programming and adjusting temperature measures detected from PT100.
It can be viewed only if parameter
R023
=
3:XMDO+PT100 or
4:XMDO+PT100+Pout or
5:XMDO+ADE+PT100 or
6:XMDO+ADE+PT100+Pout (see the Expansion Board Configuration Menu).
5.10.2.
List of Programmable Parameters P320 to P327
Paramete
r
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P320
Ch1: Measure Mode
ENGINEERING
920
0: no input
P320a
Ch1: Alarm Level
ENGINEERING
918
260°C
P321
Ch1: Offset
ENGINEERING
921
0.00°C
P322
Ch2: Measure Mode
ENGINEERING
922
0: no input
P322a
Ch2: Alarm Level
ENGINEERING
919
260°C
P323
Ch2: Offset
ENGINEERING
923
0.00°C
P324
Ch3: Measure Mode
ENGINEERING
924
0: no input
P324a
Ch3: Alarm Level
ENGINEERING
928
260°C
P325
Ch3: Offset
ENGINEERING
925
0.00°C
P326
Ch4: Measure Mode
ENGINEERING
926
0: no input
P326a
Ch4: Alarm Level
ENGINEERING
929
260°C
P327
Ch4: Offset
ENGINEERING
927
0.00°C
Table 24: List of parameters P320 to P327
P320/P322/P324/P326 Measure Mode for Channels 1/2/3/4
P320 / P322 /
P324 / P326
Range
0
1
0: no input
1: val PT100
Default
0
0: no input
Level
ENGINEERING
Address
920/922/924/926
Function
This parameter selects the type of analog signal available in terminals
27
–28, 29–30, 31–32, 33–34 in ES847 option board:
0:
No signal is used.
1
: The acquired signal is transformed into degrees centigrade.
(See Measures
M069
-
M072
).