SAFEDOCK®
Safegate Group
Manual
Date: 6 February 2015
Chapter: 2 INSTALLATION
Version: 2.7
Page 19 of 26
Note:
GOS/SAM is an optional system that may not exist at your airport.
4.2
EARTHING THE SAFEDOCK HOUSING
It is supposed that the support fixture, used for mounting the Safedock unit, is
connected to construction ground/earth for the current drain from lighting induced
voltage surges. Alternatively, a copper cable of minimum 25 mm
2
connected to earth,
must be available.
The Safedock unit shall be connected to earth (the earth connection point is delivered
by a third party), using an “earth bonding strap” with a conductor area of
25 mm
2
, which shall be connected to the ground point on the rear of the Safedock
housing.
4.3
SAFEDOCK CONNECTION TO MAINS
The mains supply should be routed from its conduit entry point via the routing channel
to the pole circuit breaker (mains disconnect device). Route it away from other
conductors and components. A cable, 3 x 1.5 mm
2
, shall be used (or dimensions acc
to local standard). It shall be connected to the Safedock unit or see Chapter 5
DRAWINGS. The protect earth (PE) wire shall be connected to chassis directly, as it
enters the cabinet, to the yellow/green terminal. The cable inside the cabinet shall be
as short as possible.
The PE/cable gland hole is located at the rear/lower area,
in the Safedock unit, as in the figure.
Note
: If the PE hole is not used, it is important to seal it
using the rubber plug/bolt supplied in the Operator Panel
package.
FIGURE 2.19 PE EXAMPLE
4.3.1
Main Switch Specification
A main switch shall be installed near the Safedock unit and shall be easily accessed
by service personnel. The switch should have following specifications:
Minimum Voltage Rating: 240 VAC
Minimum Amperage Rating: 10 A
Disconnects all phases and neutral simultaneously
Marked/labelled as the main switch for the Safedock system
4.4
CONNECTION OF COMMUNICATION LINES
4.4.1
General
The following signals, associated with the Operator Panel, are to be connected to the
Safedock main unit:
24 VDC power.
Operator Panel communication lines.
Emergency Stop line.
Dead-man-switch line (option).
Maintenance COM line.
Summary of Contents for safedock
Page 1: ...SAFEDOCK Manual...
Page 2: ...Note This page is blank for convenient double sided printing...
Page 225: ......
Page 227: ......
Page 228: ......
Page 232: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 244: ......
Page 245: ......
Page 250: ......
Page 251: ......
Page 252: ......
Page 253: ......
Page 254: ......
Page 255: ......
Page 256: ......
Page 257: ......
Page 259: ......
Page 260: ......
Page 261: ......
Page 263: ......
Page 264: ......
Page 266: ......
Page 267: ......
Page 268: ......
Page 271: ...CANCEL ENTER...
Page 272: ......
Page 273: ...K73 K74...
Page 274: ......
Page 276: ......
Page 277: ......
Page 278: ......
Page 279: ...K73...
Page 280: ......
Page 282: ......
Page 283: ......
Page 284: ......
Page 287: ......
Page 288: ......
Page 289: ......
Page 290: ......
Page 293: ......
Page 294: ......
Page 295: ......
Page 298: ......
Page 299: ......
Page 300: ......
Page 302: ......
Page 304: ......
Page 310: ......
Page 311: ......
Page 312: ......
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ......
Page 317: ......
Page 318: ......
Page 319: ......
Page 320: ......
Page 321: ......
Page 322: ......
Page 323: ......
Page 324: ......
Page 325: ......
Page 326: ......
Page 327: ......
Page 328: ......
Page 329: ......
Page 335: ......
Page 336: ......
Page 337: ......
Page 340: ......
Page 346: ......
Page 347: ......