6.6.4 GSD file for ProfiNet IO
The GSD file contains the specific configuration data of the device. The data must be known to the
Profibus controller.
The manufacturers of the controller supply the tools for the integration of the GSD file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The GSD file is supplied on a CD or can be downloaded from the Roland homepage.
Note
24 Bytes I/O must be set.
By pressing the key “
▼
” status indicators are shown on the display.
Status Indicators
Nr.
LED
State
Description
LED 1 Link /
Activity
Green Link
established
Green, flashing
Receiving/Transmitting data
Off
No link or power off
LED 2 Communi-
cation
Status
Green
On line, Run
- Connection with IO Controller established
- IO Controller is in RUN state
Green, 1 flash
On line, STOP
- Connection with IO Controller established
- IO Controller in STOP state
Off
Off line
- No connection to IO Controller
LED 3 Module
Status
Green
Initialized, no error
Green, 1 flash
Diagnostic data available
Green, 2 flashes
Blink. Used by an engineering tool to identify the
Anybus module
Red , 1 flash
Configuration error
- Too many modules / submodules
- IO size derived from IO Controller too large
- Configuration mismatch ( no module, wrong module)
Red, 3 flashes
No Stations Name or no IP-Address assigned
Red, 4 flashes
Internal error
Off
No power or not initialized
LED 4 ---
---
---