Program parameter 5:
Setting the lower limit value.
Fig. 41: Adjusting the lower limit
Value range: between 1% and 100% of the nominal value, with simultaneously displaying the
absolute limit value.
Program parameter 6:
Setting the upper limit value.
Fig. 42: Adjusting the upper limit
Value range: between 100% and 180% of the nominal value, with simultaneously displaying the
absolute limit value.
Program parameter 7:
Adjusting the time for average value.
Fig. 43: Adjusting the time for average value
Possible choices are:
•
8 / 15 / 25 / 50 / 100 / 250 ms
Generally, the „desired value“ should be set to fit to the transportation speed and to the sheet
length.
Note
Fast transportation and short sheets require a smaller averaging
time, see chapter 8.3.
Program Parameter: 5
lower threshold
80% 0.720 mm
Program Parameter: 6
upper threshold
120% 1.080 mm
Program Parameter: 7
average value
25ms