7.8
Adjustment parameters
Adjustment parameters are parameters, which are only valid for this individual system; they cannot
be transferred to other systems.
Adjustment parameter 1:
Measuring channel calibration
This is required before operating a new system, to replace a sensor or a control unit. Start by
placing a calibration sheet between the sensors. The thickness of the calibration sheet is stored in
the unit.
Depending on the sensor type, following sensor distances are allowed:
•
LAAS10 / :
10 mm
±
1 mm
•
LAAS40 / :
40 mm
±
2.5 mm
•
LAAS200 /:
200 mm
±
10 mm
•
The measuring channel calibration is valid to all programs.
Note
LAAS10 / and LAAS200 / are in preparation.
Fig. 44: Selection of measuring channel
Display:
•
missing:
Measuring channel calibration at one measuring channel has not
been performed yet.
•
ok:
Measuring channel calibration at one measuring channel has been
performed.
To perform measuring channel calibration press the ENTER key.
Following possibilities can be selected:
•
no:
Do not perform measuring channel calibration.
•
yes:
Perform (again) measuring channel calibration at selected channels.
(for L20-XX-S).
•
measuring channel: (1 / 2 / 3 / 1+2 / 1+3 / 2+3 / 1+2+3):
Perform (again) measuring channel calibration at selected channels.
(for L20-3-XX-S and depending on selected sensors).
L20-XX-S
L20-3-XX-S
Fig. 45: Enter the thickness of calibration sheet
Enter the thickness of the calibration sheet at measuring channel calibration.
adjust parameter: 1
measuring channel
calibration
ok
adjust parameter: 1
thickness of
calibration sheet
0.500mm
adjust parameter: 1
thickness of
calibration sheet
0.500mm ENTER start