Manual
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
B0063191 / 1.3
Communication with the PLC
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
49
Inputs (PLC
L20)
Outputs (L20
PLC)
Byte.Bit
Meaning
Byte.Bit
Meaning
BIN0.0
Service selection
(Bit 32,1,0)
0000 = empty service
0001 = read parameters
0010 = write parameters
0100 = open parameter channel
1000 = close parameter channel
BOUT0.0
Service selection
(Bit 3,2,1,0)
0000 = empty service
0001 = read parameters
0010 = write parameters
0100 = open parameter channel
1000 = close parameter channel
BIN0.1 BOUT0.1
BIN0.2 BOUT0.2
BIN0.3 BOUT0.3
BIN0.4
Set
Application data length
always to
11 (11 = 4 Byte)
BOUT0.4
Set
Application data length
always to
11 (11 = 4 Byte)
BIN0.5 BOUT0.5
BIN0.6
Handshake
The state is changed with
every new job. It is controlled by the
master only, when a new job is to be
processed by the R1000. The R1000
mirrors the handshake back, once the job
is processed. At a successful job, the
collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1.
Further jobs can only be done by
withdrawal of the faulty service.
BOUT0.6
Handshake
The state is changed with every
new job. It is controlled by the master only,
when a new job is to be processed by the
R1000. The R1000 mirrors the handshake
back, once the job is processed. At a successful
job, the collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1. Further
jobs can only be done by withdrawal of the
faulty service.
BIN0.7 --
BOUT0.7
Collision
0 = Fault free access, 1 = Faulty access.
"1" is set by the R1000 only if a service is
invalid or not executable. In this case the
master must reset the service to end the faulty
condition. See also the section "Reset faulty
access" within this chapter.
BIN1.0-7
Program index
Back reflexion
0 = Program 1, 255 = System parameter
BOUT1.0-7
Program index
0 = Program 1, 255 = System parameter
BIN2.0-7
Parameter index
0...255,
Assignment see section 11.1
“Parameter channel commands"
BOUT2.0-7
Parameter index
1 ... 18 at program parameter
1 ... 24 at system parameter
Assignment see section 11.1
“Parameter channel commands"
BIN3.0-7
Application data byte 0 (MSB)
BOUT3.0-7
Application data byte 0 (MSB)
BIN4.0-7
Application data byte 1
BOUT4.0-7
Application data byte 1
BIN5.0-7
Application data byte 2
BOUT5.0-7
Application data byte 2
BIN6.0-7
Application data byte 3 (LSB)
BOUT6.0-7
Application data byte 3 (LSB)
BIN7.0-7 Checksum
BOUT7.0-7 Checksum