Manual
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Communication with the PLC
B0063191 / 1.3
36
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
6.2
Data transmission communication
The L20 uses an IN/OUT configuration for the cyclical data exchange with the master. This means
that for each transmission direction a parameter channel with
8 Bytes
as well as a process channel
with
16 Bytes
is used.
The R100 is controlled via the process channel and via the parameter channel all system and
application data is available.
The following table shows the layout of the communication facility:
Inputs (PLC
L20)
Outputs (L20
PLC)
Byte
Meaning
Byte
Meaning
Parameter c
hannel
BIN0 Management
BOUT0 Management
BIN1
Program index
BOUT1
Program index
BIN2
Parameter index
BOUT2
Parameter index
BIN3
Application data byte 0
BOUT3
Application data byte 0
BIN4
Application data byte 1
BOUT4
Application data byte 1
BIN5
Application data byte 2
BOUT5
Application data byte 2
BIN6
Application data byte 3
BOUT6
Application data byte 3
BIN7 Checksum
BOUT7 Checksum
Process ch
an
ne
l
BIN8
Control
BOUT8
Control signals (0-sheet, 1-sheet, 2-sheet)
BIN9
Program selection 1 – 255
BOUT9
Actual measuring program
BIN10 --
BOUT10 Measuring
value,
Measuring channel 1 High Byte
BIN11 --
BOUT11 Measuring
value,
Measuring channel 1 Low Byte
BIN12
Control Measuring channel 1
BOUT12 Control signal channel 1
BIN13 --
BOUT13
Measuring value, Measuring channel 1 High Byte
(identical with BOUT10)
BIN14 --
BOUT14
Measuring value, Measuring channel 1 Low Byte
(identical with BOUT11)
BIN15
Control Measuring channel 2*
BOUT15 Control signal channel 2*
BIN16 --
BOUT16 Measuring
value,
Measuring channel 2 High Byte*
BIN17 --
BOUT17 Measuring
value,
Measuring channel 2 Low Byte*
BIN18
Control Measuring channel 3*
BOUT18 Control signal channel 3*
BIN19 --
BOUT19 Measuring
value,
Measuring channel 3 High Byte*
BIN20 --
BOUT20 Measuring
value,
Measuring channel 3 Low Byte*
BIN21 --
BOUT21 --
BIN22 --
BOUT22 --
BIN23 --
BOUT23 --
* only for L20-3-XX-S unit version
6.3
Process channel
The process channel is implemented via the bytes 8 to 23.