Double Sheet Control System R1000 series L20
with integrated fieldbus interface
B0063191 / 1.3
Communication with the PLC
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
37
6.3.1 Process channel – functions and signals
Byte 8 to 11:
Inputs (PLC
L20)
Ausgänge (L20
PLC)
Byte.Bit Meaning
Byte.Bit
Meaning
BIN8.0
System test
BOUT8.0
Function result
BIN8.1
Measurement start
BOUT8.1
Always „1“(High)
BIN8.2
Calibration
6)
BOUT8.2
Function fault (1 = Fault)
BIN8.3
Dummy function
3)
BOUT8.3
Ready (0 = Fault)
1)
BIN8.4
---
BOUT8.4
Warning
2)
BIN8.5
Clear 2-Blech / clear 0-1-2-outputs
BOUT8.5
0-sheet
2)
(summary output
5)
)
BIN8.6
Program switch
BOUT8.6
1- sheet
2)
(summary output
5)
)
BIN8.7
Reset function fault
BOUT8.7
2- sheet
2)
(summary output
5)
)
BIN9.0
Measuring program number for program
switching
BOUT9.0
Actual measuring program
BIN9.1 BOUT9.1
BIN9.2 BOUT9.2
BIN9.3 BOUT9.3
BIN9.4 BOUT9.4
BIN9.5 BOUT9.5
BIN9.6 BOUT9.6
BIN9.7 BOUT9.7
BIN10.0
---
BOUT10.0
High Byte Messwert
4)
Measuring channel 1
BIN10.1
---
BOUT10.1
BIN10.2
---
BOUT10.2
BIN10.3
---
BOUT10.3
BIN10.4
---
BOUT10.4
BIN10.5
---
BOUT10.5
BIN10.6
---
BOUT10.6
BIN10.7
---
BOUT10.7
BIN11.0
---
BOUT11.0
Low Byte measuring value
4)
Measuring channel 1
BIN11.1
---
BOUT11.1
BIN11.2
---
BOUT11.2
BIN11.3
Dummy Function
3)
BOUT11.3
BIN11.4
Dummy Function
3)
BOUT11.4
BIN11.5
---
BOUT11.5
BIN11.6
---
BOUT11.6
BIN11.7
Range (only L20-3-XX-S)
BOUT11.7
Explanation of summary output 0-sheet, 1-sheet and 2-sheet:
If the unit is operated in the sequencer mode (program with more sensors e.g. 1+2+3), the measurement result is formed as
summary output. Only the active sensors are included.
2-sheet
is issued if at least one sensor detects 2-sheet.
1-sheet
is issued if all sensors detect 1-sheet.
0-sheet
is issued if no 2-sheet is detected but at least one sensor detects 0-sheet.
If the results of individual sensors are required, then interrogate bytes 12-23.
1)
If a fault occurs at the equipment an operator intervention is required e.g. memory error, low or missing voltage.
2),3), 4)
Footnotes see next chart “Byte 12 to 14”
5)
At R1000 systems with multiple measuring points, these outputs are issued as "summary output" for all measuring points;
as this equipment has only one measuring point available, the result of the measuring point 1 will be outputted.
6)
This function is implemented only in L20-3-XX-S (L20-XX-S in preparation).