6.6.2 EDS file for DeviceNet
The EDS file contains the specific configuration data of the slaves. The data must be known to the
DeviceNet master.
The manufacturers of the DeviceNet master supply the tools for the integration of the EDS file into
the DeviceNet network. Suitable are for example the Allen-Bradley DeviceNet manager. Roland
Electronic does not supply such tools, because they have to be compatible with the interface
design of the master.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
Note
24 Bytes I/O must be set.
By pressing the key “
▼
” status indicators are shown on the display.
Status Indicators
Nr.
LED
State
Description
LED 1 ---
---
Not used
LED 2 Network
Status
(NS)
Off
Not powered, not on line
Green
On line, one or more connection established
Green, flashing
On line, no connection established
Red
Critical link failure
Red, flashing
One or more connections timed out
Alternating
Red / Green
Device self-test in progress
LED 3 Module
Status
(MS)
Off No
power
Green Normal
operation
Green, flashing
Auto Baud in progress
Red Major
fault
Red, flashing
Minor fault
Alternating
Red / Green
Device self-test in progress
LED 4 ---
---
Not used