Fault messages, causes and remedies
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
107
No. Cause
Remedy
214 Measuring channel 1
Communication problems
In case of repeated appearance please contact Roland
Electronic
215 Measuring channel 2
216 Measuring channel 3
217 Measuring channel 1
Is not configured
Do not remove sensors during operating. Eventually
restart
218 Measuring channel 2
219 Measuring channel 3
220 Measuring channel 1: Sensor for beam control defect
Replace sensor with beam control
221 Measuring channel 2: Sensor for beam control defect
222 Measuring channel 3: Sensor for beam control defect
223 Measuring channel 1: Beam of sensor A not free
Nothing must be between the sensors
224 Measuring channel 1: Beam of sensor B not free
225 Measuring channel 1: Beam of sensors not free
226 Measuring channel 2: Beam of sensor A not free
227 Measuring channel 2: Beam of sensor B not free
228 Measuring channel 2: Beam of sensors not free
229 Measuring channel 3: Beam of sensor A not free
230 Measuring channel 3: Beam of sensor B not free
231 Measuring channel 3: Beam of sensors not free
232 Measuring channel 1:
Sensor A and B interchanged
Measuring channel 1: Replace connection A and B
233 Measuring channel 2:
Measuring channel 2: Replace connection A and B
234 Measuring channel 3:
Measuring channel 3: Replace connection A and B
9.11 Other faults
No. Cause
Remedy
Unknown error or error description is included in a newer
manual.
• Contact Roland Electronic Service Department.
• Request new documentation.