B0063191 / 1.3
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
73
7.5
General information regarding the configuration
Note
The correct configuration depends on the communication with the PLC,
on the measurement task and the connected components.
The following rules apply to the operation in the configuration mode:
•
The configuration mode is activated (while in measurement mode) by pressing the MENU
key.
•
The configuration mode is terminated or cancelled by pressing the MENU key.
•
The selected / set parameters can be changed when the items are blinking in the display.
•
The selected / set parameters are activated by pressing the ENTER key.
Note
The systems info and bus info is displayed by pressing the
ENTER
key in
the base menu (also see system parameter 27).
Note
In the base menu the LED of the fieldbus coupler is displayed when
pressing
the
▼
key, see chapter 6.6 “Fieldbus configuration files”.
7.6
Changing, setting-up or checking the configuration
In order to select, set-up or check the system / program parameters, press the MENU key.
Here either reviewing or changing the configuration can be selected.
Configuration review:
No changings can be performed.
The measurement mode is not interrupted.
Fig. 34: Indication after calling-up the menu
Configuration change
:
After entering the password it is possible to perform changings.
The following menu option is shown.
Fig. 35: Setting the configuration mode
configuration
review
configuration
change