7. COMMUNICATION DATA LIST
IMR01Y09-E3
73
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
240
(0x00F0)
Number of communication
measured data items (IN)
when conducting polling
I/O communication
1, 2
1
R/W 0: Depends on the DIP switch setting
1 to 5:
5 words
6 to 200: 6 to 200 words
0
241
(0x00F1)
Number of communication
setting data items (OUT)
when conducting polling
I/O communication
1, 2
1
R/W 0: Depends on the DIP switch setting
1 to 5:
5 words
6 to 200: 6 to 200 words
0
242
(0x00F2)
RUN/STOP logic
selection
1, 2
1 R/W 0: RUN
=
0, STOP
=
1
1: RUN
=
1, STOP
=
0
Valid to RUN/STOP (ID: 234) and the
4th word and the 5th word in the polling
I/O communication setting item (OUT).
However, invalid to the RUN/STOP
transfer (ID: 36).
0
243
(0x00F3)
Setting validity selection
1
1 R/W 0: The setting is validated when the
power is turned off once after the
setting is changed and it is turned on
again.
1: The setting is validated just after the
setting is changed.
Object data
•
The data of “Controller
communication item setting object
(0xC7)”
•
The data of “Number of polling I/O
communication controllers (ID: 236)”
0
244
(0x00F4)
Unused
245
(0x00F5)
Controller address
setting
1, 2
1
R/W 0 to 99 (0: No communication)
1 to 31
246
(0x00F6)
Action mode selection
1, 2,
♦
1 R/W Bit data
b0: Address setting method transfer
0:
Continuous
setting
1: Free setting
b1: PID/AT transfer polling I/O
communication
0:
Invalid
1:
Valid
b2 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 3]
0
247
(0x00F7)
Automatic acquisition of
controller address
1, 2
1
R/W 0: Do not execute the automatic acquisition
1: Execute the automatic acquisition
0
1
Valid only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned
on again.
: It is possible to set in the communication environment setting by the rotary switch of
COM-JH (See P. 23) or configuration tool (See P. 33).
♦
:
Communication environment setting by rotary switch of COM-JH is possible.