7. COMMUNICATION DATA LIST
IMR01Y09-E3
63
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
137
(0x0089)
Force ON of Event 4
action
31 R/W
Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual
mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the
setting change rate limiter is being
operated
b4 to b15: Unused
Data
0: Invalid
1: Valid
[Decimal number: 0 to 15]
0
138
(0x008A)
CT1 ratio
31
R/W 0 to 9999
CTL-6-P-N:
800
CTL-12-S56-
10L-N:
1000
139
(0x008B)
CT1 assignment
31
R/W 0: None
1: OUT1
2: OUT2
3: DO1
4: DO2
5: DO3
6: DO4
1
140
(0x008C)
Heater break alarm 1
(HBA1) type
31 R/W 0: Heater break alarm 1 (HBA1) type A
(Time-proportional control output)
1: Heater break alarm 1 (HBA1) type B
(Continuous control output and
time-proportional
control
output)
1
141
(0x008D)
Number of heater break
alarm 1 (HBA1) delay
times
31
R/W 0 to 255 times
5
142
(0x008E)
CT2 ratio
31
R/W 0 to 9999
CTL-6-P-N:
800
CTL-12-S56-
10L-N:
1000
Continued on the next page.