8. USAGE EXAMPLE
IMR01Y09-E3
76
8.2 System Configuration
DeviceNet
Controller communication (RS-485: Modbus)
OMRON
SYSMAC CJ series
Personal computer
PLC (Master)
Node address: 0
DeviceNet communication
speed: 125
kbps
Unit number:
0
Controller (FB400)
Communication speed
:
19200 bps (
Factory set value
)
Data bit configuration:
Data bit: 8
Parity bit: Without
Stop bit: 1
Controller
1
(Device address 1)
Controller 2
(Device address 2)
COM-JH (Slave)
Node address: 1
DeviceNet communication speed:
125
kbps
Number of communication words:
7
words
Controller communication speed:
19200
bps
(Factory set value)
Use instruments
DeviceNet communication converter:
COM-JH
×
1
Controller (temperature controller):
FB400 (Communication 1: With RS-485)
×
2
PLC
−
SYSMAC CJ (OMRON product)
CPU unit: CJ1M, DeviceNet master unit: CJ1W-DRM21
or
−
Control Logix 5550 [Rockwell Inc. (Allen-Bradley) ]
CPU module: 1756-L1, LINK module (DeviceNet): 1756-DNB
Personal computer
The configuration tool must be installed in a personal computer.
DeviceNet communication cable (thick cable)
Connection cable for connecting COM-JH and controller