APPENDIX
IMR01Y09-E3
100
Controller Object (0x64: 64Hex)
Object class
Attributes Not
supported
Services Not
supported
Object instance ( : 1 to 31)
Any object instance from 1 to 31 corresponds to any controller from 1 to 31.
If Get is made to the instance No. corresponding to the nonexistent controller No. in
communication items other than “unused,” “0” is read while no error occurs if set is made
(no data is written).
ID
Description
Get
Set
Type
Value
Attributes 1
Measured
value
(PV)
Yes
No
INT
See P. 45
2
Current transformer 1 (CT1) input value
monitor
Yes
No
INT
See P. 45
3
Current transformer 2 (CT2) input value
monitor
Yes
No
INT
See P. 45
4
Set value (SV) monitor
Yes
No
INT
See P. 45
5
Remote setting (RS) input value monitor
Yes
No
INT
See P. 45
6
Burnout state monitor
Yes
No
WORD
See P. 45
7
Burnout state monitor of feedback
resistance input
Yes
No
WORD
See P. 45
8
Event 1 state monitor
Yes
No
WORD
See P. 45
9
Event 2 state monitor
Yes
No
WORD
See P. 45
10
Event 3 state monitor
Yes
No
WORD
See P. 45
11
Event 4 state monitor
Yes
No
WORD
See P. 45
12
Heater break alarm 1 (HBA1) state monitor
Yes
No
WORD
See P. 45
13
Heater break alarm 2 (HBA2) state monitor
Yes
No
WORD
See P. 45
14
Manipulated output value (MV1) monitor
[heat-side]
Yes
No
INT
See P. 45
15
Manipulated output value (MV2) monitor
[cool-side]
Yes
No
INT
See P. 45
16
Error code
Yes
No
WORD
See P. 46
17
Digital input (DI) state monitor
Yes
No
WORD
See P. 46
18
Output state monitor
Yes
No
WORD
See P. 46
19
Operation mode state monitor
Yes
No
WORD
See P. 46
20
Memory area soak time monitor
Yes
No
INT
See P. 46
21
Integrated operating time monitor
Yes
No
INT
See P. 46
22
Holding peak value ambient temperature
monitor
Yes
No
INT
See P. 47
23
Power feed forward input value monitor
Yes
No
INT
See P. 47
24
Backup memory state monitor
Yes
No
INT
See P. 47
25
Unused
No
No
UINT
26
Unused
No
No
UINT
27
Unused
No
No
UINT
28
Unused
No
No
UINT
29
Unused
No
No
UINT
30
Unused
No
No
UINT
Continued on the next page.