5. SETTING
IMR01Y09-E3
25
Continued from the previous page.
Node address setting switch MSD
Node address setting switch LSD
No.
Setting item
Data range
Factory
set value
6 Controller
communication
transmission wait time
0 to 5: 0 to 20 ms (
=
set value
×
4)
6: 30
ms
7: 50
ms
8: 70
ms
9: 100
ms
Set the standby time until the COM-JH
starts sending data after receiving data from
the controller.
0
7
Unused
Don’t set this one
8
Controller address setting
0:
Controller 1 to 31: 1 to 31
1: Controller
1:
1
Controller 2 to 31: 0
2
~
8: Don’t set this one
9:
Automatic acquisition of controller
address
Set the address of the controller that is
connected to COM-JH to have
communication take place with only that
address.
Set “9: Automatic acquisition of controller
address” and turn on the power again to
acquire the connected controller address
automatically.
0
9
Set value initialization
0 to 8: Unused
9: Communication
environment
setting initialization execution
Initialize each communication environment
setting data item which can be set by the
rotary switch.
The number of communication words can be calculated from the following equation.
Number of communication words
=
Number of communication items
×
Number of communication controllers
+
Fixed communication date items: 5 words*
* Measured data items (IN)
Receive counter:
1 word
Alarm state:
2 words
RUN/STOP state:
2 words
Setting data items (OUT)
Setting state selection: 3 words
RUN/STOP transfer: 2 words
The number of polling I/O communication controllers, the number of communication
measured data items (IN) and the number of communication setting data items (OUT) can
also be set via Explicit message communication, or by the configuration tool.