7. COMMUNICATION DATA LIST
IMR01Y09-E3
68
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
185
(0x00B9)
Proportional band limiter
(high) [heat-side]
31 R/W
TC/RTD:
Input span
V/I: 1000.0 %
186
(0x00BA)
Proportional band limiter
(low) [heat-side]
31 R/W
TC/RTD inputs:
0 to input span, 0.0 to input span or
0.00 to input span (Unit:
°
C [
°
F])
Varies with the setting of the
integral/derivative time decimal point
position selection.
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of input span
TC/RTD:
0
V/I: 0.0 %
187
(0x00BB)
Integral time limiter (high)
[heat-side]
31 R/W
3600
188
(0x00BC)
Integral time limiter (low)
[heat-side]
31 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point
position selection.
0
189
(0x00BD)
Derivative time limiter
(high) [heat-side]
31 R/W
3600
190
(0x00BE)
Derivative time limiter
(low) [heat-side]
31 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point
position selection.
0
191
(0x00BF)
Proportional band limiter
(high) [cool-side]
31 R/W
TC/RTD:
Input span
V/I: 1000.0 %
192
(0x00C0)
Proportional band limiter
(low) [cool-side]
31 R/W
TC/RTD inputs:
1 to input span, 0.1 to input span or
0.01 to input span (Unit:
°
C [
°
F])
Varies with the setting of the
integral/derivative time decimal point
position selection.
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of input span
TC/RTD:
1
V/I: 0.1 %
193
(0x00C1)
Integral time limiter (high)
[cool-side]
31 R/W
3600
194
(0x00C2)
Integral time limiter (low)
[cool-side]
31 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point
position selection.
0
195
(0x00C3)
Derivative time limiter
(high) [cool-side]
31 R/W
3600
196
(0x00C4)
Derivative time limiter
(low) [cool-side]
31 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point
position selection.
0
197
(0x00C5)
Open/Close output neutral
zone
31
R/W 0.1 to 10.0 % of output
2.0
198
(0x00C6)
Open/Close output
differential gap
31
R/W 0.1 to 5.0 % of output
1.0
199
(0x00C7)
Action at feedback
resistance (FBR) input
break
31 R/W 0: Action depending on the valve
action at STOP
1: Control action continued
0
200
(0x00C8)
Feedback adjustment
31
R/W 0: Adjustment end
1: Open-side adjustment start
2: Close-side adjustment start
201
(0x00C9)
Control motor time
31
R/W 5 to 1000 seconds
10