8. USAGE EXAMPLE
IMR01Y09-E3
77
8.3 Setting of Use Instruments
Setting of the PLC, COM-JH and controller is shown in the following.
PLC setting
[DeviceNet communication requirement]
•
Node address:
0
•
DeviceNet communication speed: 125 kbps
•
Unit number:
0
•
Communication cycle time:
(Number of COM-JH communication words
×
1.2
+
50) [ms]
or more
=
7
×
1.2
+
50
=
58.4 [ms] or more
For setting procedure, see
PLC Instruction Manual.
COM-JH setting
[DeviceNet communication requirement]
•
Node address:
1
•
DeviceNet communication speed: 125 kbps
•
Number of communication words: 7 words
•
Controller address:
1, 2 (Controller 1, Controller2)
•
Action mode:
0
(Address setting method Continuous setting, PID/AT transfer by polling I/O communication: Invalid)
•
Automatic acquisition of controller address:
0: Do not execute the automatic acquisition
For setting procedure, see
5. SETTING (P. 20)
and
6.2. Communication Method (P.27)
.
[Controller communication requirement]
•
Communication speed:
19200 bps (factory set value)
For setting procedure, see
5.3 DIP Switch Setting
(P. 22)
.
Controller (FB400) setting
[Controller communication requirement: Use communication 1 side]
•
Node address:
1 and 2
•
Communication protocol:
Modbus-RTU
•
Communication speed:
19200 bps (factory set value)
•
Data bit configuration:
Data 8-bit, without parity, stop 1-bit
For setting procedure, see
FB400/FB900 Communication Quick Manual (IMR01W07-E )
.