7. COMMUNICATION DATA LIST
IMR01Y09-E3
67
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
175
(0x00AF)
AT cycles
31
R/W 0: 1.5 cycles
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
1
176
(0x00B0)
Output value with AT
turned on
31 R/W Output value with AT turned off to
+
105.0 %
Actual output values become those
restricted by the output limiter.
Position proportioning control:
Becomes valid only when there is
feedback resistance (FBR) input and
no feedback resistance (FBR) input is
disconnected (high limit of feedback
resistance input at AT).
105.0
177
(0x00B1)
Output value with AT
turned off
31 R/W
−
105.0 % to Output value with AT
turned on
Actual output values become those
restricted by the output limiter.
Position proportioning control:
Becomes valid only when there is
feedback resistance (FBR) input and
no feedback resistance (FBR) input is
disconnected (low limit of feedback
resistance input at AT).
−
105.0
178
(0x00B2)
AT differential gap time
31
R/W 0.0 to 50.0 seconds
10.0
179
(0x00B3)
Proportional band
adjusting factor [heat-side]
31 R/W
1.00
180
(0x00B4)
Integral time adjusting
factor [heat-side]
31 R/W
1.00
181
(0x00B5)
Derivative time adjusting
factor [heat-side]
31 R/W
1.00
182
(0x00B6)
Proportional band
adjusting factor [cool-side]
31 R/W
1.00
183
(0x00B7)
Integral time adjusting
factor [cool-side]
31 R/W
1.00
184
(0x00B8)
Derivative time adjusting
factor [cool-side]
31 R/W
0.01 to 10.00 times
1.00
Continued on the next page.