7. COMMUNICATION DATA LIST
IMR01Y09-E3
72
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
232
(0x00E8)
Controller alarm state
1
2
RO Bit data
Object instance 1:
b0 to b15: Controller 1 to 16
Object instance 2:
b0 to b14: Controller 17 to 31
Data 0: OFF
1: ON
[Decimal number: 0 to 65535]
OR
of Controller state 1 (ID: 225)
233
(0x00E9)
Error state
1
2
RO Bit data
Object instance 1:
b0 to b15: Controller 1 to 16
Object instance 2:
b0 to b14: Controller 17 to 31
Data 0: OFF
1: ON
[Decimal number: 0 to 65535]
OR
of Controller state 2 (ID: 226)
234
(0x00EA)
RUN/STOP
1
2
R/W Bit data
Object instance 1:
b0 to b15: Controller 1 to 16
Object instance 2:
b0 to b14: Controller 17 to 31
Data RUN/STOP state is depending on
the value of RUN/STOP logic
selection
(ID:
242)
•
ID: 242
=
0
0: RUN (control start)
1: STOP (control stop)
•
ID: 242
=
1
0: STOP (control stop)
1: RUN (control start)
[Decimal number: 0 to 65535]
Link RUN/STOP transfer (ID: 36)
0
235
(0x00EB)
Setting update flag
1
1
RO 0: Setting update is completed
1: During setting update
236
(0x00EC)
Number of polling I/O
communication
controllers
1
1
R/W 1 to 31
10
237
(0x00ED)
Unused
238
(0x00EE)
COM-JH error code
1
1
RO Bit data
b0: Back-up error
b1: Controller communication error
b2 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 3]
239
(0x00EF)
Number of connected
controller in controller
communication
1
1
RO 0 to 31
1
Valid only when Explicit message communication is used.
Continued on the next page.