7. COMMUNICATION DATA LIST
IMR01Y09-E3
45
Communication data (Controller Object 0x64)
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
1
(0x0001)
Measured value (PV)
31
RO Input scale low to Input scale high
2
(0x0002)
Current transformer 1
(CT1) input value monitor
31 RO
3
(0x0003)
Current transformer 2
(CT2) input value monitor
31 RO
CTL-6-P-N:
0.0 to 30.0 A
CTL-12-S56-10L-N:
0.0 to 100.0 A
4
(0x0004)
Set value (SV) monitor
31
RO Setting limiter (low) to Setting limiter
(high)
5
(0x0005)
Remote setting (RS) input
value monitor
31 RO Setting limiter (low) to Setting limiter
(high)
6
(0x0006)
Burnout state monitor
31
RO 0: OFF
1: ON
7
(0x0007)
Burnout state monitor of
feedback resistance input
31 RO 0: OFF
1: ON
8
(0x0008)
Event 1 state monitor
31
RO 0: OFF
1: ON
9
(0x0009)
Event 2 state monitor
31
RO
10
(0x000A)
Event 3 state monitor
31
RO
11
(0x000B)
Event 4 state monitor
31
RO
12
(0x000C)
Heater break alarm 1
(HBA1) state monitor
31 RO 0: OFF
1: ON
13
(0x000D)
Heater break alarm 2
(HBA2) state monitor
31 RO
14
(0x000E)
Manipulated output value
(MV1) monitor [heat-side]
31 RO PID control or heat/cool PID control:
−
5.0 to +105.0 %
Position proportioning control with
feedback resistance (FBR) input:
FBR input value is displayed.
0.0 to 100.0 %
15
(0x000F)
Manipulated output value
(MV2) monitor [cool-side]
31 RO
−
5.0 to +105.0 %
16
(0x0010)
Error code
31
RO Bit data
b0: Adjustment data error
b1: Back-up error
b2: A/D conversion error
b3: Unused
b4: Unused
b5: Custom data error
b6: Unused
b7: Watchdog timer error
b8: Program error (stack)
b9 to b10: Unused
b11: Program error (busy)
b12 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 4095]
Continued on the next page.