7. COMMUNICATION DATA LIST
IMR01Y09-E3
61
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
127
(0x007F)
Event 3 hold action
31
R/W 0: OFF
1: Hold action ON
(At power turned on)
2: Re-hold action ON
(At power turned on and SV changed)
Depends on
model code.
When not
specifying: 0
128
(0x0080)
Event 3 interlock
31
R/W 0: Unused
1: Used
0
129
(0x0081)
Event 3 differential gap
31
R/W
Deviation, process or set value:
0 to Input span (Unit:
°
C [
°
F])
MV: 0.0 to 110.0 %
: TC/RTD:
2
°
C [
°
F]
V/I:
0.2
%
: 0.2 %
130
(0x0082)
Event 3 delay timer
31
R/W 0.0 to 600.0 seconds
0.0
131
(0x0083)
Force ON of Event 3
action
31 R/W Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual
mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the
setting change rate limiter is being
operated
b4 to b15: Unused
Data
0: Invalid
1: Valid
[Decimal number: 0 to 15]
0
Continued on the next page.