7. COMMUNICATION DATA LIST
IMR01Y09-E3
69
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
202
(0x00CA)
Integrated output limiter
31
R/W 0.0 to 200.0 % of control motor time
(0.0: OFF)
Becomes invalid when there is feedback
resistance (FBR) input.
150.0
203
(0x00CB)
Valve action at STOP
31
R/W 0: Close-side output OFF,
Open-side
output
OFF
1: Close-side output ON,
Open-side
output
OFF
2: Close-side output OFF,
Open-side
output
ON
Becomes valid when there is no feedback
resistance (FBR) input or the feedback
resistance (FBR) input is disconnected.
0
204
(0x00CC)
Startup tuning (ST)
31
R/W 0: Startup tuning (ST) unused
1: Execute once *
2: Execute always
* Automatically reverts to 0 after Startup
tuning (ST) ends.
The startup tuning (ST) function is
activated according to the ST start
condition selected.
If control is other than position
proportioning control, set to RO (Only
reading data is possible).
0
205
(0x00CD)
ST proportional band
adjusting factor
31 R/W
1.00
206
(0x00CE)
ST integral time adjusting
factor
31 R/W
1.00
207
(0x00CF)
ST derivative time
adjusting factor
31 R/W
0.01 to 10.00 times
1.00
208
(0x00D0)
ST start condition
31
R/W 0: Activate the startup tuning (ST)
function when the power is turned on;
when transferred from STOP to RUN;
or when the set value (SV) is changed.
1: Activate the startup tuning (ST)
function when the power is turned on;
or when transferred from STOP to
RUN.
2: Activate the startup tuning (ST)
function when the set value (SV) is
changed.
0
209
(0x00D1)
Automatic temperature
rise group
31 R/W 0 to 16
(0: Automatic temperature rise function
OFF)
0
210
(0x00D2)
Automatic temperature
rise learning
31 R/W 0: Unused
1: Learning *
* Automatically reverts to 0 after automatic
temperature rise learning ends.
If the Automatic temperature rise group
corresponds to “0: Automatic
temperature rise function OFF,” set to
RO (Only reading data is possible).
1
Continued on the next page.