6. DeviceNet COMMUNICATION
IMR01Y09-E3
36
Continued from the previous page.
Set measured data items in order starting from IN ch1 (Parameter 1). If any of the
following values is set, all items from that item to IN ch32 (Parameter 32) are the same as
those when set at “0.”
•
If at “0”
•
If set to attribute ID to which no communication data items are assigned
•
If at 231 to 236 or 238 to 243 as attribute ID
For attribute ID of the communication data items, see
7. COMMUNICATION DATA
LIST (P. 44)
.
2.
Set the setting data item (OUT) on the same COM-JH parameter setting screen.
•
Set attribute ID “45” of “Set value (SV)” in “OUT ch1 (Parameter 33).”
•
Set attribute ID “39” of “Event 1 set value” in “OUT ch2 (Parameter 34).”
•
“0” is set to unused OUT ch (Parameter 35 to 64).
In addition to “Setting state selection” and “RUN/STOP transfer” assigned as fixed, up to
32 types of setting data items can be selected.
Set the setting data items in order starting from OUT ch1 (Parameter 33). If any of the
following values is set, all items from that item to OUT ch32 (Parameter 64) are the same
as those when set at “0.”
•
If at “0”
•
If set to attribute ID to which readable communication data items are assigned
•
If set to attribute ID to which no communication data items are assigned
•
If at 36, 231 to 236 or 238 to 243 as attribute ID
•
If at 33 as attribute ID (when “b1: PID/AT transfer by polling I/O communication” of
attribute ID “246” (Action mode selection) is “0: Invalid”
For attribute ID of the communication data items, see
7. COMMUNICATION DATA
LIST (P. 44)
.
Continued on the next page.
Parameter Value
33 OUT
ch1
45
34 OUT
ch2
39
35 OUT
ch3
0
36 OUT
ch4
0
64 OUT
ch32
0
Attribute ID of Set value (SV): 45
Attribute ID of Event 1 set value: 39
Set “0” in unused items