7. COMMUNICATION DATA LIST
IMR01Y09-E3
53
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
75
(0x004B)
Set lock level
31
R/W Bit data
b0: Lock only setting items
other than SV and event
set value (EV1 to EV4).
b1: Lock only event set value
(EV1 to EV4)
b2: Lock only set value (SV)
b3 to b15: Unused
Data 0:
Unlock
1:
Lock
[Decimal number: 0 to 7]
0
76
(0x004C)
STOP display
31
R/W 0: “SToP” is displayed on the PV
display.
1: “SToP” is displayed on the SV
display.
1
77
(0x004D)
Bar graph display
31
R/W 0: No display
1: MV1 or MV2
2: PV
3: SV monitor
4: Deviation value
5: CT1 input value
6: CT2 input value
1
78
(0x004E)
Bar graph display
resolution
31 R/W 1 to 100 digit/dot
Becomes valid when the bar graph
display is “4: Deviation value,” “5: CT1
input value” or “6: CT2 input value.”
100
79
(0x004)
Direct key 1
31
R/W 0: Unused
1: A/M transfer key
(Type 1, Type 2)
1
80
(0x0050)
Direct key 2
31
R/W 0: Unused
1: MONI key (For type 1) or
R/L transfer key (For type 2)
1
81
(0x0051)
Direct key 3
31
R/W 0: Unused
1: AREA key (For type 1) or
RUN/STOP transfer key (For type 2)
1
82
(0x0052)
Direct key type
31
R/W 1: Type 1
2: Type 2
1
Continued on the next page.