7. COMMUNICATION DATA LIST
IMR01Y09-E3
55
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
85
(0x0055)
Decimal point position
31
R/W 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
•
K (
−
200.0 to
+
800.0
°
C,
−
328.0 to
+
800.0
°
F), J (
−
200.0 to
+
800.0
°
C,
−
328.0 to
+
1200.0
°
F), T, E (
−
200.0 to
+
700.0
°
C,
−
328.0 to
+
1292.0
°
F), U, L
Only 0 or 1 can be set.
•
Other than the above
Only 0 can be set.
RTD input:
•
Pt (
−
100.00 to
+
100.00
°
C,
−
199.99 to
+
199.99
°
F), JPt (
−
100.00 to
+
100.00
°
C,
−
199.99 to
+
199.99
°
F)
From 0 to 2 can be set.
•
Other than the above
Only 0 or 1 can be set.
Voltage (V)/current (I) inputs:
From 0 to 4 can be set.
Depends on
model code.
When not
specifying:
TC/RTD: 0
V/I: 1
86
(0x0056)
Input scale high
31
R/W TC/RTD inputs:
Input scale low to Maximum value of
the selected input range
Voltage (V)/current (I) inputs:
−
19999 to +19999
(Varies with the setting of the decimal
point position)
TC/RTD:
Maximum
value of the
selected input
range
V/I: 100.0
87
(0x0057)
Input scale low
31
R/W TC/RTD inputs:
Minimum value of the selected input
range to Input scale high
Voltage (V)/current (I) inputs:
−
19999 to +19999
(Varies with the setting of the decimal
point position)
TC/RTD:
Minimum value
of the selected
input range
V/I: 0.0
88
(0x0058)
Input error determination
point (high)
31 R/W Input scale low
−
(5 % of input span) to
Input scale high + (5 % of input span)
TC/RTD: Input
scale high +
(5 % of input
span)
V/I: 105.0
89
(0x0059)
Input error determination
point (low)
31 R/W TC/RTD:
Input
scale low
−
(5 % of input
span)
V/I:
−
5.0
Continued on the next page.