7. COMMUNICATION DATA LIST
IMR01Y09-E3
52
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
69
(0x0045)
RS bias
Cascade control:
Cascade bias
Ratio setting:
Ratio setting bias
31 R/W
−
Input span to +Input span
0
70
(0x0046)
RS digital filter
Cascade control:
Cascade digital filter
Ratio setting:
Ratio setting digital
filter
31 R/W 0.0 to 100.0 seconds
(0.0: Unused)
0.0
71
(0x0047)
RS ratio
Cascade control:
Cascade ratio
Ratio setting:
Ratio setting ratio
31 R/W 0.001
to
9.999
1.000
72
(0x0048)
Proportional cycle time
[heat-side]
31
R/W 0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
This item becomes RO (Only reading
data is possible) for the voltage/current
output specification.
M output:
20.0
V, T, D output:
2.0
73
(0x0049)
Proportional cycle time
[cool-side]
31
R/W 0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
If control is other than heat/cool PID
control, set to RO (Only reading data is
possible).
This item becomes RO (Only reading
data is possible) for the voltage/current
output specification.
M output:
20.0
V, T, D output:
2.0
74
(0x004A)
Manual manipulated
output value
31 R/W PID control:
Output limiter (low) [MV1] to
Output limiter (high) [MV1]
Heat/cool PID control:
−
Output limiter (high) [MV2] to
+
Output limiter (high) [MV1]
(
−
105.0 to
+
105.0 %)
When the control motor with feedback
resistance (FBR) is used:
Output limiter (low) [MV1] to
Output limiter (high) [MV1]
0.0
Continued on the next page.