Engineer Programming
Page 86
3.
From with the Parameters sub-menu, Press the
1) One by One
menu option. The
following display appears:
ZONE ONE BY ONE
ZONE#=01 (XY:ZZ)
Note
The display next to the selected zone number defines the type of zone and its location in
the system in the format
XY:ZZ
X: Zone physical type (E=Wired zone, W=Wireless zone, B=Bus zone, I=Input zone or
single BUS zone expander)
Y: The expander ID number. “0” represent the main bus, for example:
E0:04
refer to wired zone 04 on the main board.
B0:15
refers to bus zone 15 on the main bus.
ZZ : The serial zone number in the system (01-32)
4.
Specify a two-digit zone number from which you want to start programming (for
example, 01) and press
to access the category of Zone Label.
5.
Enter the zone label. The Labels category enables you to create and/or edit up to 15
characters to describe each of the system's zones (see page 80)
6.
Press
to confirm and proceed to the partitions category. The Partitions menu
contains parameters that enable you to program the partition assignment for each zone.
The following display appears:
P=1234 Z=XX
Y...
Note
The
XX
in the
Z=XX
designation is for the zone number.
In a multi-partition system, a zone can be assigned to more than one partition.
A system without partitions is regarded as having a single partition (meaning Partition
1)
Using the
,
,
, or
keys, select (
Y
) or deselect the relevant partitions
to which this zone will belong.
7.
Press
to confirm and proceed to the groups category. The following display
appears:
GROUP=ABCD Z=01
....
Select the group(s) for which the designated zone is to be in effect by using the
key
to toggle
Y
(es) and advance through the entries with the
key.
Note:
Each partition has 4 groups. The zone group definition is common to each of the
partitions assigned to the zone.