Installation and Operation Manual
Page 45 of 156
[PVI-XXX.0-YY(-TL) - Rev:1.0]
6.2.1
Multi-Master System
In this configuration there is no physical link between the photovoltaic fields in each module. Each
DC disconnecting switch is practically independent of the others.
The following table indicates, in the first column, the position of the switches, in the second
whether the photovoltaic field is connected to the module, and in the third whether it can be
removed or inserted in the seat.
Table 6-1: ADMITTED OPERATIONS AND POSITION OF THE DC SWITCHES
MULTI - MASTER
P
OSITION OF
D
ISCONNECTING
SWITCHES
DC
(
Figure 6-8
)
P
HYSICAL
CONNECTION
BETWEEN
DC
SOURCE AND
M
ODULE
W
ITHDRAWAL
/
I
NSERTION OF
M
ODULES
*
H
(high)
L
(low)
H
(high)
L
(low)
A
NO
NO
YES*
YES*
B
NO
YES
YES*
NO
C
YES
NO
NO
YES*
D
YES
YES
NO
NO
*before withdrawal wait 5 minutes after the disconnecting switch was set to 0 (OFF)