Off: The system pump is not locked.
On: When the generator lock is active the system pump is also locked.
Mixing valve boost (2130)
For the admixture the boiler flow temperature actual value must be higher
than the requested setpoint of the mixer flow temperature, since this can
not be corrected otherwise. The controller forms the boiler temperature
setpoint from the boost set here and the current flow temperature setpoint.
Actuator running time (2134)
Setting the actuator running time of the mixing valve used.
Primary contr/system pump (2150)
Before buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically upstream of the buffer storage tank.
After buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically downstream of the buffer storage tank.
9.2.11 Boiler
Release below outside temp (2203)
The boiler is only put into operation if the mixed outside temperature is be
low the threshold set here. The switching difference is 0.5°C.
Full charging buffer (2208)
Under prog. no. 4810 (full charging buffer storage tank) is selected, wheth
er and when the buffer storage tank is fully charged despite automatic
generator lock. Under prog.no. 2203 it is set whether the boiler takes part
in the full charging or not.
Off: The boiler does not take part in the full charging of the buffer stor
age tank.
On: The boiler takes part in the full charging of the buffer storage tank.
Setpoint min (2210) andSetpoint max (2212)
As a protection function the boiler temperature setpoint can be limited be
low by the minimum setpoint (prog.no. 2210) and above by the maximum
setpoint (prog.no. 2212).
Setpoint manual control (2214)
Temperature to which the boiler is controlled in manual control mode.
Burner running time min (2241)
Here, the period following the commissioning of the burner is selected dur
ing which the shutdown differential is increased by 50%. However, this
setting cannot guarantee that the burner remains operational for the selec
ted period.
Burner off time min (2243)
The boiler minimum pause time only takes effect between heating require
ments coming following in sequence. The boiler minimum pause time
blocks the boiler for a set time.
SD burner off time (2245)
When a switching difference is exceeded,Burner off time min (prog. no.
2243) is aborted. The boiler starts despite pausing time.
Pump overrun time (2250) andPump overr time after HW
(2253)
The delay times of the pumps are controlled according to heating mode or
drinking water mode.
Boiler pump on heat gen lock (2301)
Stop of boiler pump in case of activated manual heat generation lock (e.g.
via H1).
Off: Switching off not activated
9 Settings
96
7636047 - 02 - 24082015
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...