1. Press the information key.
Further information about the fault is displayed
See
Fault code table
For more information, see
Fault code table, page 138
11.2.2 Fault switch-off
A fault switch-off is a safety-switch off in the case of flame failure during
operation. After every safety switch-off a new ignition attempt is carried out
as per program. If this does not result in flame formation a fault switch-off
occurs.
In case of fault switch-off, the reset button on the control panel should be
pressed.
In case of operation disturbances (bell symbol in the display), the digit in
the display on the operating panel indicates the cause of the disturbance
(see fault code table).
Burner does not start:
No voltage at the control and regulating centre
No “burner ON” signal from the heating circuit control (see
Fault code ta
ble
)
Gas tap closed
No ignition
Burner goes into fault mode:
Without flame formation:
No ignition
Ionization electrode has ground connection
Ionization electrode is not connected
No gas
Gas pressure too low
In spite of flame formation the burner goes into fault mode after expiration
of the safety time:
Ionization electrode defective or soiled
Ionization electrode does not penetrate the flame
Ionization electrode is not connected
Gas pressure not stable
11 Troubleshooting
7636047 - 02 - 24082015
141
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...