Function
Prog. no.
Setting level
EC four
125 kW
EC four
170 kW
EC four
215 kW
Natural
gas
Propane Natural
gas
Propane Natural
gas
Propane
Boiler
Output basic stage
2331
F
20
35
28
35
35
48
Burner control
Required output prepurging
9504
F
73
73
94
94
96
96
Required output ignition
9512
F
59.3
66.3
75.5
86.8
77.1
89.3
Required output LF
9524
F
20.0
35.0
28.0
35.0
35.0
48.0
Fan output/speed slope
9626
F
37.1
33.9
27.6
24.1
26.4
23.0
Fan output/speed Y-section
9627
F
501.1
453.9
517.2
507.4
464.4
446.3
CO
2
content (± 0.2)
9.3
11.0
9.3
11.0
9.3
11.0
Function
Prog. no.
Setting level
EC four
260 kW
EC four
300 kW
Natural gas
Propane
Natural gas
Propane
Boiler
Output basic stage
2331
F
42
58
48
58
Burner control
Required output prepurging
9504
F
120
120
129
129
Required output ignition
9512
F
93.4
110.0
103.9
115.5
Required output LF
9524
F
42.0
58.0
48.0
58.0
Fan output/speed slope
9626
F
20.1
19.9
19.9
19.0
Fan output/speed Y-section
9627
F
488.0
305.7
431.7
306.1
CO
2
content (± 0.2)
9.3
11.0
9.3
11.0
Caution
Risk for the environment and the device if CO content is too high!
When a boiler set for natural gas is put into operation with LPG,
the adjustment screw for full load on the gas valve must be turned
clockwise (-) by half a turn before the boiler is switched on!
7.4.4 Manual adjustment of burner output (controller stop func
tion)
For controlling the CO
2
values theEC four operated in the control stop func
tion
1. Press buttonOperating mode button heating operation for approx 3 s
The message Controller stop active is displayed.
2. Wait until the display has reached the basic display again.
3. Press the Info button
The message Controller stop setpoint appears on the display. The
actual modulation degree will be displayed on the display.
4. Press OK.
The setpoint can now be changed.
5. Press OK.
The setpoint displayed is then adopted by the controller.
xxxxxxxxxxxxxx
7 Commissioning
7636047 - 02 - 24082015
53
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...